|
This document is available for downloading
as an Adobe PDF document.

Current Transformer (CT)
Testing Using the Powermate System Analyzer
Modern current transformers (CT) produce a
secondary output current that is in-phase with and proportional to the primary
input current (ie, divided by the CT ratio) when supplying current to a circuit
with burden that does not exceed the burden rating. In a normal meter, the
burden (resistance) is very low, but long secondary leads or degraded wiring
contact integrity can increase the installed resistance. Furthermore, as in any
equipment exposed to the environment, CTs can internally degrade or even fail.
The Powermate offers three methods for
testing the integrity of an installed Current Transformer:
-
Burden Testing
-
Ratio Testing
-
Burden + Ratio Testing
Burden Testing checks only the effect of additional burden
(resistive load) on the CT secondary output current.
Ratio Testing checks only
the CT ratio (and angle) as measured from the actual CT primary and secondary
currents.
Burden+Ratio Testing simultaneously checks the CT secondary current
and ratio as additional burden is applied. If practical, Burden+Ratio Testing is
recommended since it provides ratio data that can be directly compared to the
nameplate value and the percentage ratio change plot gives unambiguous
indications of CT burdened response. Each type of test is described in detail
below and examples of the test results generated by the Powermate are
given in Figures 1 to 4:

Figure 1. Plot of Ratio Change (Burden + Ratio Test)

Figure 2. Burden + Ratio Test Summary Table

Figure 3. Plot of Burden Change (Burden Test)

Figure 4. Plot of CT Class Accuracy (Burden + Ratio Test)
Burden Testing
In Burden Testing, the secondary current from
the CT passes directly through the BURDEN input of the Powermate using the
heavy burden cable (with redundant conductors for safety). The fundamental (ie,
60 Hz only) CT secondary current is measured to determine a reference "no
applied burden" current output. A resistive burden of 0.1 ohm is
automatically applied to the current path and the CT secondary current is again
measured. Additional resistance values from 0.1 to 4.0 ohms are sequentially
applied up to the limit specified by the operator. The entire process takes less
than 2 seconds and the test results are displayed as a percentage change in CT
secondary current as a function of added burden.
The Burden Test results are interpreted by looking for a
progressive decrease in the CT secondary current (ie, negative percentage
change) as the applied burden increases. If such a progressive decrease is
observed, the test indicates that the CT output is decreasing with applied load.
If the drop is significant at less than the rated burden of the CT, then a
problem exists in the CT or its wiring. If a progressive decrease is not
observed (ie, change stays near zero), the test indicates stable CT output even
with additional burden.
One problem that occurs in field Burden
Testing (but not in a lab test) is that the test is dependent on the actual
field currents which depend on customer demand. If the customer demand changes
during the test interval, the CT primary current changes which directly changes
the CT secondary current. This change in current will appear to be caused by the
change in burden since only the secondary current is being measured. The
Powermate reduces the likelihood of this problem due to its short test interval (2
seconds) and incorporation of numerous tests to identify customer demand
changes. However, if the customer demand changes, there will be a sudden,
erratic, or positive jump in the percentage current change (ie, not flat or a
smooth decrease). If this occurs, simply repeat the test until a Burden Test is
complete under more stable customer demand conditions. (An example of a customer
demand change that cannot be reliably detected by Burden Testing is shown in
Figure 3. As shown by Figure 1, Burden+Ratio testing can eliminate this
problem.)
Ratio Testing
In Ratio Testing, both the primary and secondary currents
from a CT are simultaneously measured by the Powermate. The
fundamental (ie, 60 Hz only) currents are used to calculate the ratio and phase
angle between the primary and secondary of the CT. This value can be directly
compared to the nameplate ratio to verify the proper field performance of the
CT. Additionally, the phase (angle) shift can be verified to be low. Since the
ratio results can be directly compared, there is no complicated data
interpretation required.
In most situations, Ratio Testing can be performed using the
same direct (BURDEN) secondary CT current input as is used in Burden Testing
(even though any current input may be used). At the same time, the CT primary
current is measured using any compatible current probe (or multiple probes). The
Powermate measures both currents, calculates the Ratio and
phase angle, and displays the results. If a reversed polarity or a cross-phase
connection is indicated by the measured data, a warning is displayed to the
operator. Because only a comparison between 2 currents is being performed, Ratio
Testing can be performed using current probes for both the CT primary and
secondary current measurements.
In some cases, Ratio Testing can be more complicated because
measurement of the primary CT current can be physically difficult or requires an
understanding of the CT wiring. For example, the CT may be connected to a
high-voltage line or may be located in a tightly-packed pad-mount CT enclosure.
Optional probes are available to make measurements in these situations but must
be available for the operator. Furthermore, for meter installations with
"summed" currents (ie, Form 5 metering on a 4-wire Y service), the
first CT primary current consists of phase A current in the forward direction
and phase B current in the reverse direction. The person performing the Ratio
Test must be familiar with the installation to connect the test current probe
around ALL of the primary current conductors in the proper direction.
Alternately, 2 probes can be used to independently measure currents with the
Powermate performing internal current summations.
Burden + Ratio Testing
In Burden+Ratio Testing, the burden and ratio
analyses are performed at the same time. Since a Burden Test is being performed,
the CT secondary current must be directly connected to the Powermate
BURDEN input. As for Ratio Testing, the CT primary current must be measured
using appropriate probe(s). When started, the testing is performed automatically
with sequential burdens applied. As in the Burden Test, the total test time is
less than 2 seconds.
The results of the Burden+Ratio Test include all of the data
described for the separate tests plus an additional display of percentage change
in ratio as a function of applied burden and a Class Accuracy (see Figures 1 and
4). The display of percentage change in ratio removes the problems associated
with customer demand changes that may occur in Burden Testing since the ratio is
calculated from the secondary current relative to the primary current.
Therefore, the percent change in ratio plot may be directly interpreted by
looking for a progressive increase (ie, secondary current drop produces a higher
ratio) without external variations causing ambiguous results.
CT Testing: Ratio Testing Probe
Considerations
The Powermate has
connections to allow a variety of current probes for CT Ratio testing. In most
cases the "Burden" or "Phase Current" inputs are used to
measure CT secondary currents, but ratio testing usually requires a larger or
higher voltage rated probe to measure CT primary currents. The available current
Input Connectors are:
| "Current _x" |
[Secondary] current input up to 1 amp
from clamp-on current probes or precision IQ Safety Plug probes (normal
inputs for 3_ power measurements)
|
| "Burden" |
[Secondary] direct current input up to 25
amps from CT secondary
|
| "5Amp" |
[Primary] current input up to 5 amps from
clamp-on current probes or precision CT's. (330 Only)
|
| "Process" |
[Primary] (BNC) voltage input (±10V)
from clamp-on current probes (voltage output type), High Voltage (optical)
current probes, or other sensors.
|
| "IQ Voltage" |
[Primary] voltage input (±4V) from
FLEX-5000 current probes |
CAUTION:
ALL CABLES MUST BE CONNECTED TO POWERMATE
BEFORE CONNECTING TO SERVICE
When a probe is required to perform a CT
Ratio test (Main Menu, Option 5), the following steps should be performed:
Select the proper probe for the CT conductor (i.e., opening size, rated
current, and maximum voltage rating).
Connect the probe to one of the Powermate inputs using the proper test
cable.
If the selected probe is normally used for CT Ratio testing, its calibration
(amplitude and phase) should be stored in the Powermate. If not, use the CTRL
key, Option 2, to enter (or to verify) the probe calibration.
Connect the current probe around the CT conductor(s) with the arrow pointing
toward the higher potential (i.e., source). For HV Optic Probes, the black
button faces the source.
In the CT Test Menu (from Main Menu 5), select the Input Connector and probe
type being used.
Start the CT Test and the Powermate will apply amplitude and phase
corrections to the probe output before being used in the CT analysis.
Some precautions to be observed when using current probes are:
-
Verify the probe is rated for the voltage and current being tested.
-
Never connect a current probe around a conductor before terminating it to
its cable and to the Powermate.
-
For High-Voltage optical current probes, verify the optic cable is clean to
prevent surface arcing.
-
Position the probe head perpendicular to the current carrying conductor as
nearly in the center of the probe opening as practical.
-
For clamp-on probes, clean contact surfaces and then snap and release the
jaws to verify a metal-to-metal contact of the jaws (dirt and insects may
contaminate the surfaces.)
-
For flexible probes, the plastic closure connector should be fully closed
and be positioned as far as possible from the conductor (also observe #7 below).
-
Position the probe as far as practical from other current carrying
conductors. (All current probes will respond to external currents.)
-
For High-Voltage optical current probes, press the black button on the head
assembly to force the 2000A range when currents are above 100 amps. (Note that
the decimal is not displayed on the receiver unit when the 2000A range is
active.)
-
For HV Optical Current Probes, position the open end such that it is not
pointing toward other current carrying conductors.
-
IN GENERAL, if a CT Ratio test has an erroneous ratio result or a
phase angle greater than ±1°, check the installation of the current
probe before suspecting a CT problem.
Other
Documents Available for CT Testing
| Introduction to Instrument
Transformers |
 |
| Selecting the Appropriate CT
for the Metering Installation |
 |
|