Burden Testing checks only the effect of additional burden
(resistive load) on the CT secondary output current.
Ratio Testing checks only
the CT ratio (and angle) as measured from the actual CT primary and secondary
currents.
Burden+Ratio Testing simultaneously checks the CT secondary current
and ratio as additional burden is applied. If practical, Burden+Ratio Testing is
recommended since it provides ratio data that can be directly compared to the
nameplate value and the percentage ratio change plot gives unambiguous
indications of CT burdened response. Each type of test is described in detail
below and examples of the test results generated by the PowerMaster® are
given in Figures 1 to 4:
|
 |
 |
|
Figure 1. Burden + Ratio Test Results
|
Figure 2. Burden + Ratio Test Summary Table
|
| |
|
| |
|
|
 |
 |
|
Figure 3. Plot of Burden Only Test
|
Figure 4. Plot of
CT Class Accuracy
(Burden + Ratio Test)
|
Burden Testing
In Burden Testing, the secondary current from
the CT passes directly through the CURRENT input of the PowerMaster® using
the Current Direct probes. The CT secondary current is measured to determine a reference "no
applied burden" current output. The user may select to view the current
with or without harmonics (fundamental only). A resistive burden of 0.1 ohm is
automatically applied to the current path and the CT secondary current is again
measured. Additional resistance values from 0.1 to 4.0 ohms are sequentially
applied up to the limit specified by the operator. The entire process takes less
than 2 seconds and the test results are displayed as a percentage change in CT
secondary current as a function of added burden.
The Burden Test results are interpreted by looking for a
progressive decrease in the CT secondary current (ie, negative percentage
change) as the applied burden increases. If such a progressive decrease is
observed, the test indicates that the CT output is decreasing with applied load.
If the drop is significant at less than the rated burden of the CT, the
PowerMaster® will alert the user a
problem exists in the CT or its wiring. If a progressive decrease is not
observed (ie, change stays near zero), the test indicates stable CT output even
with additional burden.
One problem that occurs in field Burden
Testing (but not in a lab test) is that the test is dependent on the actual
field currents which depend on customer demand. If the customer demand changes
during the test interval, the CT primary current changes which directly changes
the CT secondary current. This change in current will appear to be caused by the
change in burden since only the secondary current is being measured. The
PowerMaster® reduces the likelihood of this problem due to its short test interval (2
seconds) and incorporation of numerous tests to identify customer demand
changes. However, if the customer demand changes, there will be a sudden,
erratic, or positive jump in the percentage current change (ie, not flat or a
smooth decrease). If this occurs, simply repeat the test until a Burden Test is
complete under more stable customer demand conditions. (An example of a customer
demand change that cannot be reliably detected by Burden Testing is shown in
Figure 3. As shown by Figure 1, Burden+Ratio testing can eliminate this
problem.)
Ratio Testing
In Ratio Testing, both the primary and secondary currents
from a CT are simultaneously measured by the PowerMaster® . The currents
(with or without the presence of harmonics) are used to calculate the ratio and phase
angle between the primary and secondary of the CT. This value can be directly
compared to the nameplate ratio to verify the proper field performance of the
CT. Additionally, the phase (angle) shift can be verified. Since the
ratio results can be directly compared, there is no complicated data
interpretation required.
In most situations, Ratio Testing can be performed using the
same direct (CURRENT) secondary CT current input as is used in Burden Testing
(even though any current input may be used). At the same time, the CT primary
current is measured using any compatible current probe (or multiple probes). The PowerMaster® measures both currents for validity, calculates the Ratio and
phase angle, and displays the results. If a reversed polarity or a cross-phase
connection is indicated by the measured data, an error is displayed to the
operator. If the nameplate ratio is measured outside of the user selectable
limits, an error will also be displayed. Because only a comparison between 2 currents is being performed, Ratio
Testing can be performed using current probes for both the CT primary and
secondary current measurements.
In some cases, Ratio Testing can be more complicated because
measurement of the primary CT current can be physically difficult or requires an
understanding of the CT wiring. For example, the CT may be connected to a
high-voltage line or may be located in a tightly-packed pad-mount CT enclosure.
Optional probes are available to make measurements in these situations but must
be available for the operator. Furthermore, for meter installations with
"summed" currents (ie, Form 5 metering on a 4-wire Y service), the
first CT primary current consists of phase A current in the forward direction
and phase B current in the reverse direction. The person performing the Ratio
Test must be familiar with the installation to connect the test current probe
around ALL of the primary current conductors in the proper direction.
Alternately, 2 probes can be used to independently measure currents with the
PowerMaster® performing internal current summations.
Burden + Ratio Testing
In Burden+Ratio Testing, the burden and ratio
analyses are performed at the same time. Since a Burden Test is being performed,
the CT secondary current must be directly connected to the PowerMaster®
CURRENT input. As for Ratio Testing, the CT primary current must be measured
using appropriate probe(s). When started, the testing is performed automatically
with sequential burdens applied. As in the Burden Test, the total test time is
less than 2 seconds per phase.
The results of the Burden+Ratio Test include all of the data
described for the separate tests plus an additional display of percentage change
in ratio as a function of applied burden and a Class Accuracy (see Figure
4). The display of percentage change in ratio removes the problems associated
with customer demand changes that may occur in Burden Testing since the ratio is
calculated from the secondary current relative to the primary current.
Therefore, the percent change in ratio plot may be directly interpreted by
looking for a progressive increase (ie, secondary current drop produces a higher
ratio) without external variations causing ambiguous results.