Direct Current Probes are designed to be inserted
directly into test switches for more accurate current measurements than
clamp-on probes. Handles are tapered to provide safe insertion.
Transformer Ratio: 1000:1
Accuracy: ± 0.05%
Watt-hr Accuracy Using Direct Current Probes
Current
PF
= 1.00
PF
= 0.50
20.00
0.05%
0.10%
15.00
0.05%
0.05%
10.00
0.05%
0.05%
5.00
0.05%
0.05%
2.50
0.05%*
0.05%*
1.00
0.05%
0.05%
0.50
0.05%
0.05%
0.25
0.05%*
0.05%
0.10
0.30%
0.40%
* Defined
test points for class 20 meters according to ANSI C12-01-2001
Powermetrix, A Division of TEC
10737 Lexington Drive
Knoxville, TN 37932-3294