MN313 Specifications

Measurement Range:
0.1 to 240A; 200A nominal


Output Signal:
1 mA/A (100mA @ 100A AC)

Accuracy (200A Range):

0.1 to 1A:

±2% reading, ±0.02mA

1 to 80A:

±1% reading, ±0.02mA

80 to 100A:

±2% reading, ±0.1mA

100 to 150A:

±2.5% reading, ±0.5mA

150 to 200A:

Not Specified

Phase Shift (200A Range):

0.1 to 1A

Not Specified

1 to 20A

≤ 3.0°

20 to 80A

≤ 2.0°

50 to 150A

≤ 2.5°


 

Frequency Range:
40 to 10,000 Hz

Working Voltage:
600 V max.

Jaw Opening:
0.83" (21mm)

Max Conductor Size:
0.78" (20mm)

Transformation Ratio:
1000:1 
    
Operating Temperature:
14° to 131° F (-10° to 55° C)

Storage Temperature:
-40° to 158° F (-40° to 70° C)

Dimensions:
5.47 x 2.00 x 1.18" (139 x 51 x 30 mm)

Weight:
6.5 oz (180g)

Colors:
Dark gray handles, red jaws

 

 
  Powermetrix, A Division of TEC
10737 Lexington Drive
Knoxville, TN 37932-3294
  Phone:(865) 966-5856
Fax: (865) 675-1241
E-Mail: main@powermetrix.com
 
 